Suitable for U0≤1.8kV extruded insulated power cables (without insulation shielding layer)
l Single-core, two-core, three-core, four-core, five-core cable
l Copper or aluminum conductor
l No insulation shielding layer, no metal tape shielding or metal wire shielding
l Armored or unarmored
l Metal tape armoring or metal wire armoring
use:
Terminal: Installed at the end of the running cable, connected to overhead lines, load switches and other power supply equipment or busbars.
Straight-through connector: installed in the middle of the running cable, used to connect 2 sections of cable lines.
Technical Parameters
Comply with and pass JB/T7829-2006 rated voltage 1kV (Um=1.2kV) to 35kV (Um=40.5kV) power cable heat shrinkable terminal and JB/T7830-2006 rated voltage 1kV (Um=1.2kV) to 10kV Um= 12kV) heat shrinkable straight-through joint for extruded insulated power cable.
serial number | project | Standard parameter values |
1 | Power frequency withstand voltage test | 8kV, no breakdown or flashover in 5 minutes |
2 | Power frequency withstand voltage test (wet state) | 7.2kV, no breakdown or flashover in 1 minute |
3 | Constant pressure load cycle (in air) | 4.5kV, heated to 95-100℃, stable for 2 hours, cycled 60 times |
4 | Constant pressure load cycle (water) | 4.5kV, heated to 95-100℃, stable for 2 hours, cycled 10 times |
5 | Short circuit thermal stability (cable cross-section 400m㎡) | 40.9kA, 3s, 2 times |
6 |
Short circuit dynamic stability(cable cross-section 400m㎡) |
177.0kA, 10ms, 1 time |
7 | Power frequency withstand voltage test | 8kV, no breakdown or flashover in 5 minutes |