26/35 (27.5) ملحقات كابلات الانكماش البارد kV

 

Scope of application:

Suitable for extruded insulated power cables with U0≤27.5kV

ل واحد, three-core cable

L النحاس أو موصل الألومنيوم

l Extruded semi-conductive shielding layer or semi-conductive tape shielding

l Metal tape shielding or metal wire shielding

L مدرعة أو غير مدرحة

لدر درع الشريط المعدني أو درع الأسلاك المعدنية

يستخدم:

Indoor terminal: The end of a cable installed in an indoor environment (not subject to wind, frost, rain, snow and sunlight) and connected to switch cabinets, transformers and other power supply equipment or busbars.

Outdoor terminal: The end of a cable installed in an outdoor environment (able to withstand wind, frost, rain, snow and sunlight) and connected to overhead lines, busbars, transformers, fuses and other power supply equipment or overhead lines.

موصل مباشرة (insulated connector): in the middle of the installed and running cable, تستخدم للاتصال 2 أقسام من خطوط الكابل.

المعلمات الفنية:

Comply with and pass GB/T12706.4-2020 rated voltage 1kV (أم = 1.2 كيلو فولت) إلى 35 كيلو فولت (أم = 40.5kV) extruded insulated power cables and accessories Part 4: rated voltage 6kV (Um=7.2kV) إلى 35 كيلو فولت ( أم = 40.5kV) test requirements for power cable accessories and GB/T28427-2012 Electrified Railway 27.5kV single-phase AC cross-linked polyethylene insulated cables and accessories 1.

رقم سري مشروع قيم المعلمة القياسية
1 تواتر الطاقة مع اختبار الجهد 124كيلو فولت, لا يوجد انهيار أو فلاش في 5 دقائق
2 DC withstand voltage test 110كيلو فولت, لا يوجد انهيار أو فلاش في 15 دقائق
3 Partial discharge test Discharge ≤5pC at 48kV
4 Impulse voltage test 250كيلو فولت, positive and negative polarity 10 times each
5 constant voltage load cycle 65كيلو فولت, تسخين إلى 95-100 ℃, مستقر ل 2 ساعات, ركوب الدراجات 3 مرات
6 تواتر الطاقة مع اختبار الجهد 110كيلو فولت, no breakdown or flashover in 4h