Scope of application:
Suitable for extruded insulated power cables with U0≤27.5kV
л одноядерный, three-core cable
l Медный или алюминиевый проводник
l Extruded semi-conductive shielding layer or semi-conductive tape shielding
l Metal tape shielding or metal wire shielding
l Бронированный или небронированный
l Бронирование металлической лентой или армирование металлической проволокой.
использовать:
Indoor terminal: The end of a cable installed in an indoor environment (not subject to wind, frost, rain, snow and sunlight) and connected to switch cabinets, transformers and other power supply equipment or busbars.
Outdoor terminal: The end of a cable installed in an outdoor environment (able to withstand wind, frost, rain, snow and sunlight) and connected to overhead lines, busbars, transformers, fuses and other power supply equipment or overhead lines.
Прямой разъем (insulated connector): in the middle of the installed and running cable, используется для подключения 2 участки кабельных линий.
Технические параметры:
Comply with and pass GB/T12706.4-2020 rated voltage 1kV (Uм=1,2кВ) до 35кВ (А=40,5кВ) extruded insulated power cables and accessories Part 4: rated voltage 6kV (Um=7.2kV) до 35кВ ( А=40,5кВ) test requirements for power cable accessories and GB/T28427-2012 Electrified Railway 27.5kV single-phase AC cross-linked polyethylene insulated cables and accessories 1.
серийный номер | проект | Стандартные значения параметров |
1 | Испытание выдерживаемого напряжения промышленной частоты | 124кВ, никаких поломок и перекрытий 5 минуты |
2 | DC withstand voltage test | 110кВ, никаких поломок и перекрытий 15 минуты |
3 | Partial discharge test | Discharge ≤5pC at 48kV |
4 | Impulse voltage test | 250кВ, positive and negative polarity 10 times each |
5 | constant voltage load cycle | 65кВ, нагрет до 95-100℃, стабильный для 2 часы, езда на велосипеде 3 раз |
6 | Испытание выдерживаемого напряжения промышленной частоты | 110кВ, no breakdown or flashover in 4h |